S7协议规范常量

目录

[#Protocol ID:](#Protocol ID:)

[#Message Types:](#Message Types:)

[#Header Error Class:](#Header Error Class:)

[#Header Error Codes: (Further refines error)](#Header Error Codes: (Further refines error))

[#Return value of item response](#Return value of item response)

[#Job Request/Ack-Data function codes](#Job Request/Ack-Data function codes)

[#Memory Areas](#Memory Areas)

[#Transport size (variable Type) in Item data](#Transport size (variable Type) in Item data)

[#Variable ddressing mode](#Variable ddressing mode)

[#Transport size in data](#Transport size in data)

[#Block type constants](#Block type constants)

[#Sub block types](#Sub block types)

[#Block security mode](#Block security mode)

[#Block Language](#Block Language)

[#Userdata transmission type](#Userdata transmission type)

[#Userdata last PDU](#Userdata last PDU)

[#Userdata Functions](#Userdata Functions)

[#Variable table type of data](#Variable table type of data)

[#VAT area and length type](#VAT area and length type)

[#Userdata programmer subfunctions](#Userdata programmer subfunctions)

[#Userdata cyclic data subfunctions](#Userdata cyclic data subfunctions)

[#Userdata CPU subfunctions](#Userdata CPU subfunctions)

[#Userdata security subfunctions](#Userdata security subfunctions)

[#Userdata time subfunctions](#Userdata time subfunctions)

[#Flags for LID access](#Flags for LID access)

[#TIA 1200 area names](#TIA 1200 area names)


本主要介绍了S7通信协议中的常量和规定。首先,Protocol ID是用于标识正在使用的协议的字段,其中0x32代表S7协议。接下来,文中提到了各种消息类型,包括Job Request(工作请求)、Ack(确认)、Ack-Data(确认数据)、以及Userdata(用户数据)等。然后,文中又列举了一些错误类别和错误代码,例如Header Error Class和Header Error Codes、Parameter Error Codes等,它们用于指示消息头或参数中可能存在的错误。文中还给出了一些具体的函数代码和内存区域标识符,它们可以在实际应用中进行操作。总的来说,这些常量都是为了使S7通信协议在工业自动化领域中更加规范化、通用化和易于理解而设计的。

#Protocol ID:

0x32 - Protocol ID

#Message Types:

0x01 - Job Request

0x02 - Ack

0x03 - Ack-Data

0x07 - Userdata

#Header Error Class:

0x00 - No error

0x81 - Application relationship error

0x82 - Object definition error

0x83 - No ressources available error

0x84 - Error on service processing

0x85 - Error on supplies

0x87 - Access error

#Header Error Codes: (Further refines error)

#Parameter Error Codes:

0x0000 - No error

0x0110 - Invalid block type number

0x0112 - Invalid parameter

0x011A - PG ressource error

0x011B - PLC ressource error

0x011C - Protocol error

0x011F - User buffer too short

0x0141 - Request error

0x01C0 - Version mismatch

0x01F0 - Not implemented

0x8001 - L7 invalid CPU state

0x8500 - L7 PDU size error

0xD401 - L7 invalid SZL ID

0xD402 - L7 invalid index

0xD403 - L7 DGS Connection already announced

0xD404 - L7 Max user NB

0xD405 - L7 DGS function parameter syntax error

0xD406 - L7 no info

0xD601 - L7 PRT function parameter syntax error

0xD801 - L7 invalid variable address

0xD802 - L7 unknown request

0xD803 - L7 invalid request status

#Return value of item response

0x00 - Reserved

0x01 - Hardware fault

0x03 - Accessing the object not allowed

0x05 - Address out of range

0x06 - Data type not supported

0x07 - Data type inconsistent

0x0a - Object does not exist

0xff - Success

#Job Request/Ack-Data function codes

0x00 - CPU services

0xF0 - Setup communication

0x04 - Read Variable

0x05 - Write Variable

0x1A - Request download

0x1B - Download block

0x1C - Download ended

0x1D - Start upload

0x1E - Upload

0x1F - End upload

0x28 - PLC Control

0x29 - PLC Stop

#Memory Areas

0x03 - System info of S200 family

0x05 - System flags of S200 family

0x06 - Analog inputs of S200 family

0x07 - Analog outputs of S200 family

0x1C - S7 counters (C)

0x1D - S7 timers (T)

0x1E - IEC counters (200 family)

0x1F - IEC timers (200 family)

0x80 - Direct peripheral access (P)

0x81 - Inputs (I)

0x82 - Outputs (Q)

0x83 - Flags (M) (Merker)

0x84 - Data blocks (DB)

0x85 - Instance data blocks (DI)

0x86 - Local data (L)

0x87 - Unknown yet (V)

#Transport size (variable Type) in Item data

0x01 - BIT

0x02 - BYTE

0x03 - CHAR

0x04 - WORD

0x05 - INT

0x06 - DWORD

0x07 - DINT

0x08 - REAL

0x09 - DATE

0x0A - TOD

0x0B - TIME

0x0C - S5TIME

0x0F - DATE AND TIME

0x1C - COUNTER

0x1D - TIMER

0x1E - IEC TIMER

0x1F - IEC COUNTER

0x20 - HS COUNTER

#Variable ddressing mode

0x10 - S7-Any pointer (regular addressing) memory+variable length+offset

0xa2 - Drive-ES-Any seen on Drive ES Starter with routing over S7

0xb2 - S1200/S1500? Symbolic addressing mode

0xb0 - Special DB addressing for S400 (subitem read/write)

#Transport size in data

0x00 - NULL

0x03 - BIT

0x04 - BYTE/WORD/DWORD

0x05 - INTEGER

0x07 - REAL

0x09 - OCTET STRING

#Block type constants

'08' - OB

'0A' - DB

'0B' - SDB

'0C' - FC

'0D' - SFC

'0E' - FB

'0F' - SFB

#Sub block types

0x08 - OB

0x0a - DB

0x0b - SDB

0x0c - FC

0x0d - SFC

0x0e - FB

0x0f - SFB

#Block security mode

0 - None

3 - Kow How Protect

#Block Language

0x00 - Not defined

0x01 - AWL

0x02 - KOP

0x03 - FUP

0x04 - SCL

0x05 - DB

0x06 - GRAPH

0x07 - SDB

0x08 - CPU-DB DB was created from Plc programm (CREAT_DB)

0x11 - SDB (after overall reset) another SDB, don't know what it means, in SDB 1 and SDB 2, uncertain

0x12 - SDB (Routing) another SDB, in SDB 999 and SDB 1000 (routing information), uncertain

0x29 - ENCRYPT block is encrypted (encoded?) with S7-Block-Privacy

#Userdata transmission type

0x0 - Push cyclic data push by the PLC

0x4 - Request by the master

0x8 - Response by the slave

#Userdata last PDU

0x00 - Yes

0x01 - No

#Userdata Functions

0x1 - Programmer commands

0x2 - Cyclic data

0x3 - Block functions

0x4 - CPU functions

0x5 - Security

0x7 - Time functions

#Variable table type of data

0x14 - Request

0x04 - Response

#VAT area and length type

0x01 - MB

0x02 - MW

0x03 - MD

0x11 - IB

0x12 - IW

0x13 - ID

0x21 - QB

0x22 - QW

0x23 - QD

0x31 - PIB

0x32 - PIW

0x33 - PID

0x71 - DBB

0x72 - DBW

0x73 - DBD

0x54 - TIMER

0x64 - COUNTER

#Userdata programmer subfunctions

0x01 - Request diag data (Type 1)

0x02 - VarTab

0x0c - Erase

0x0e - Read diag data

0x0f - Remove diag data

0x10 - Forces

0x13 - Request diag data (Type2)

#Userdata cyclic data subfunctions

0x01 - Memory

0x04 - Unsubscribe

#Userdata block subfunctions

0x01 - List blocks

0x02 - List blocks of type

0x03 - Get block info

#Userdata CPU subfunctions

0x01 - Read SZL

0x02 - Message service

0x03 - Transition to stop

0x0b - Alarm was acknowledged in HMI/SCADA 1

0x0c - Alarm was acknowledged in HMI/SCADA 2

0x11 - PLC is indicating a ALARM message

0x13 - HMI/SCADA initiating ALARM subscription

#Userdata security subfunctions

0x01 - PLC password

#Userdata time subfunctions

0x01 - Read clock

0x02 - Set clock

0x03 - Read clock (following)

0x04 - Set clock

#Flags for LID access

0x2 - Encapsulated LID

0x3 - Encapsulated Index

0x4 - Obtain by LID

0x5 - Obtain by Index

0x6 - Part Start Address

0x7 - Part Length

#TIA 1200 area names

0x8a0e - DB

0x0000 - IQMCT

0x50 - Inputs (I)

0x51 - Outputs (Q)

0x52 - Flags (M)

0x53 - Counter (C)

0x54 - Timer (T)